product slide thumb
product slide

SOFAR 8.8KTLX-G3-AU

  • Remote firmware upgrade
  • Maximum efficiency 98.6%
  • Smart string level monitoring
  • Type II SPD for both DC and AC
  • Maximum DC input voltage 1100V
  • Natural cooling, no fans, low noise
  • Low start-up voltage, wide MPPT voltage

Recommended Max. PV input power 12000Wp
Number of MPP trackers 2
Number of DC inputs 1/1
Max. input voltage 1100V
Start-up voltage 160V
Rated input voltage 650V
MPPT operating voltage range 140V-1000V
Full power MPPT voltage range 380V-850V
Max. input MPPT current 15/15A
Max. input short circuit current per MPPT 22.5A/22.5A
Rated power 8000W
Max. AC power 8800VA
Max. Output current 13.3A
Nominal grid voltage 3/N/PE, 220V/380Vac, 230V/400Vac
Grid voltage range 310Vac-480Vac (According to local standard)
Nominal frequency 50/ 60Hz
Grid frequency range 45Hz-S5H2/S4H2z-66Hz (According to local standard)
Active power adjustable range 0~ 100%
THDi <3%
Power factor 1 default (adjustable +/-0. 8)

Technical Data

  • Performance

    Max efficiency : 98.50%
    European efficiency : 98.00%
  • Protection

    DC reverse polarity protection : Yes
    Anti-islanding protection : Yes
    Leakage current protection : Yes
    Ground fault monitoring : Yes
    PV-array string fault monitoring : Yes
    Anti reverse power function : Yes
    DC switch : Yes
    AFCI protection : Optional
    Input / output SPD : PV: type II standard, AC: type Il standard
  • Communication

    Standard communication mode : RS485/ USB/ Bluetooth, Optional: WiFi / GPRS /4G
  • General Data

    Ambient temperature range : -30°C~ +60°C
    Self-consumption at night : <IW
    Topology : Transformerless
    Degree of protection : IP65
    Allowable relative humidity range : 0~ 100%
    Max. Operating altitude : 4000m
    Noise : <40dB
    Weight : 17kg
    Cooling : Natural
    Dimension : 430°385° 182mm
    Display : LCD&Bluetooth +APP
    Standard warranty : 5 years, Optional: 7 years/ 10 years
  • Standard

    EMC : EN61000-3-2, EN61000-3-3.EN61000-3- 11, EN61000-3-12,EIN61000-6-1, EN61000-6-3
    Safety standards : 1EC62109-1/2, 1EC62116, 1EC61727, 1EC6 1683, 1EC60068(1,2,14,30)
    Grid standards : AS/NZS 4777, VDE V 0124-100, V0126-1-1, VDE-AR-N 4105, CEI 0-21/CEI0-16,UNE 206 007-1, ENS0549, G98/G99, EN50530. NB/T32004