product slide thumb
product slide

X3-PRO-30K-G2

  • Maximum efficiency is up to 98.5%.
  • Low startup voltage, ultrawide MPPT voltage range.
  • 150% DC oversizing, 110% AC overloading output.
  • In-built global MPP scan for higher yield efficiency.
  • SPD type II protection on both AC&DC.
  • ARC protection (Optional).

Max. PV array input power [Wp] 45000
Max. PV input voltage [V] 1100
Start Startup voltage [V] 200
Nominal input voltage [V] 650
MPP tracker voltage range [V] 160~980
No. of MPP trackers 2
Strings per MPP tracker 2
Max. input current per MPPT [A] 32/32/32
Max. short circuit current per MPPT [A] 40/40/40
Nominal AC output power [W] 30000
Nominal AC output current [A] 45.5/43.5
Max. AC output apparent power [VA] 30000
Max. AC output current [A] 45.5
Nominal AC voltage [V] 220/380, 230/400, 3/N/PE, 3/PE
Nominal grid frequency[Hz] 50/60
Displacement power factor 0.8 leading-0.8 lagging
THDi (Rated power) [%] <3

Technical Data

  • System Data

    Max. eMciency [%] : 98.5
    Euro eMciency [%] : 98
    Standby consumption(Night) [W] : <3
    Ingress protection : IP66
    Operating temperature range [°C] : -30~+60
    Max. operation altitude [m] : 4000
    Relative humidity [%] : 0~100
    Typical noise emission [dB] : <58
    Storage temperature [°C] : -30~+60
    Dimensions (W×H×D) [mm] : 482×417×181
    Weight [kg] : 28
    Cooling concept : Smart fan cooling
    Communication interfaces : USB / RS485 / DRM / Pocket WiFi (Optional: Pocket LAN/4G) / Adapter box (Optional)
  • Protection

    Over/under voltage protection : YES
    DC isolation protection : YES
    Grid monitoring : YES
    DC injection monitoring : YES
    Residual current detection : YES
    Anti-islanding protection : YES
    Over Temp protection : YES
    SPD (DC/AC) : Type II / Type II
    AC auxiliary power supply (APS) : Optional
    Arc-fault circuit interrupter (AFCI) : Optional
  • Standard

    Safety : IEC/EN 62109-1; IEC/EN 62109-2; NB/T 32004
    EMC : IEC/EN 61000; NB/T 32004
    Certification : "VDE4105; EN 50549; AS 4777.2; VDE4105; IEC 61727; IEC 62116; IEC 61683; IEC 60068; EN 50530; NB/T 32004 "